Backflow testing and prevention, certified and filed

Backflow devices protect the public water supply from your building. Annual testing is a legal requirement in Massachusetts, and the paperwork has to reach the water department.

Certified testersMassachusetts requires a certified tester. Ours are.
Reports filedResults submitted to the water department, not left in a van.
Repair and rebuildFailed devices rebuilt or replaced, then retested.
Annual remindersSo the notice from the town is not the first you hear of it.

What backflow is

Water in a supply system is supposed to travel one way, from the main into your building. Backflow is when that reverses and water from inside a property is drawn back into the public supply.

It happens through two mechanisms. Back-siphonage occurs when pressure in the main drops, a water main break, heavy fire department draw, or a nearby hydrant in use, creating suction that pulls water backwards out of connected buildings. Back-pressure occurs when pressure inside a building or system exceeds supply pressure, pushing water back into the main; boilers, pressure-boosted systems and certain equipment can all do this.

The reason it matters is what gets drawn back. A garden hose left in a pool or a bucket of pesticide, an irrigation system sitting in soil and fertiliser, a boiler full of treated water with corrosion inhibitor, a commercial dishwasher, a chemical mixing tank, any of those connected to the supply without protection can contaminate the drinking water of an entire neighbourhood.

This is why backflow prevention is regulated rather than optional. The device protects everyone else from your building, which is also why the water department cares about it and why the annual test report has to reach them.

Who needs a device

Requirements are set by state regulation and administered locally, so your water department is the authority on what applies to your property. In general terms, protection is required wherever there is a cross-connection between the potable supply and anything that could contaminate it.

Commonly required on:

  • Irrigation and lawn sprinkler systems, the most common residential requirement by a wide margin.
  • Boilers and closed heating systems, particularly where chemical treatment is used.
  • Fire sprinkler systems.
  • Commercial kitchens and food service equipment.
  • Commercial and industrial premises generally, often with a device at the service entry.
  • Medical, dental and laboratory facilities.
  • Car washes, laundries, salons and similar businesses.
  • Swimming pool fill lines and hot tubs.
  • Wells cross-connected to municipal supply, and any auxiliary water source.
  • Hose bibs, which typically need simple vacuum breakers rather than a full assembly.

If you own a commercial property in Massachusetts and have never had a backflow test, it is worth establishing your position before the water department does. Notices and, in some municipalities, service interruption are the enforcement mechanisms.

Notice from the water department? We test, report and file it.

Book a test this week

Types of assembly

Different hazard levels call for different devices, and fitting the wrong class is a common finding on older installations.

Atmospheric vacuum breaker. The simplest device, used on low-hazard applications like some irrigation zones and hose connections. It must be installed above the highest downstream outlet and cannot be under continuous pressure.

Pressure vacuum breaker. Common on irrigation systems, can be under continuous pressure, must be installed above the highest head, and protects against back-siphonage only.

Double check valve assembly. Two independently operating check valves with test cocks, used for low to moderate hazard applications and protecting against both back-siphonage and back-pressure.

Reduced pressure zone assembly: RPZ. The workhorse for high-hazard applications: two check valves plus a relief valve that discharges if either check fails. It protects against both mechanisms and is what most commercial and boiler applications require. It discharges water when it operates, so it needs an appropriate drain and it must not be installed in a pit where discharge cannot escape.

Air gap. A physical separation rather than a valve, and the most reliable protection where it can be used, which is why dishwasher installations use them.

The testable assemblies, double check, pressure vacuum breaker and RPZ, are the ones subject to annual certification.

Annual testing and the law

Massachusetts requires testable backflow prevention assemblies to be tested periodically, generally annually, and semi-annually for some higher-hazard applications, by a tester holding current state certification. The results have to be submitted to the water purveyor.

What the test involves: the tester isolates the assembly, connects a calibrated differential gauge to the test cocks, and verifies that each check valve holds against a specified pressure differential and that the relief valve on an RPZ opens at the correct point. It takes a modest amount of time per device and produces a pass or fail against defined criteria.

Three practical points that cause most of the problems we see. First, the report has to be filed, a test that was performed but never submitted counts, from the water department's perspective, as no test at all. Second, water is off during testing, which for a commercial premises means scheduling around operations. Third, a failed device must be repaired and retested, and there is usually a deadline attached.

Keeping a schedule matters. Devices come due at the same time each year, and letting them lapse invites notices and, in some municipalities, enforcement. We keep the dates and prompt in advance, which is considerably less stressful than a letter with a deadline on it.

Why devices fail

Backflow assemblies are mechanical devices with rubber seals and springs sitting in a water supply, and they wear out.

The common causes of failure: debris and grit lodging on a check valve seat, which is the single most frequent finding; rubber discs and seals hardening or degrading with age; corrosion inside the body, particularly on older assemblies or in aggressive water; spring fatigue; freeze damage, which is a serious issue in Massachusetts on any device installed outdoors or in an unheated space; and physical damage from vehicles or landscaping equipment.

Freeze damage deserves emphasis. An irrigation backflow assembly left charged over a Massachusetts winter will very likely be destroyed, and the repair is more expensive than the winterisation that would have prevented it. Any outdoor assembly needs draining and protecting before the first hard freeze: see pipe insulation and freeze protection.

Most failures are repairable with a rebuild kit, new seals, discs and springs, which is considerably cheaper than replacement. Where the body is corroded or the assembly is obsolete, replacement is the answer. Either way it needs retesting afterwards.

Irrigation systems

Irrigation is where most residential property owners first encounter backflow requirements, and it is a genuine hazard rather than a technicality: sprinkler heads sit in soil that may contain fertiliser, pesticide and animal waste, and a pressure drop in the main can draw that back.

What matters practically. The assembly must be the correct type and installed at the correct height above the highest sprinkler head, which is a common installation error. It needs annual testing where the municipality requires it. And it must be winterised, the system blown out and the assembly drained and protected before freezing weather.

The Massachusetts seasonal rhythm is worth planning around: winterise in October or early November, and reactivate and test in spring. Booking the spring test at the same time as the reactivation saves a visit, and it gets the report filed early rather than in the summer rush when every tester in the state is busy.

Boilers and heating systems

Closed heating systems need backflow protection because the water in them is not potable, it contains corrosion inhibitor, antifreeze in some systems, and the products of decades of internal corrosion, and the make-up water connection is a direct cross-connection to the supply.

The standard arrangement is a backflow preventer on the fill line, and on systems with chemical treatment or glycol this is typically an RPZ. It needs testing on the same annual cycle as any other assembly.

One consequence worth understanding: a backflow preventer, like a pressure-reducing valve, creates a closed system, so thermal expansion has nowhere to go. That makes a correctly sized and correctly charged expansion tank essential, and a waterlogged expansion tank on a system with backflow protection produces pressure spikes, weeping relief valves and premature component failure. See boiler repair and water heater installation.

For commercial buildings, backflow assemblies usually sit alongside a broader compliance picture: see commercial plumbing.

Irrigation system? Winterise the assembly before the first hard freeze.

Book winterisation

Backflow questions

If you have a testable assembly, commonly on irrigation, boilers, fire sprinklers or commercial premises, then yes, generally annually.

Your water department is the authority on what applies to your property, and they are the ones who receive the report.

A tester holding current Massachusetts certification, using a calibrated gauge.

The result has to be submitted to the water purveyor, a test that was never filed counts as no test at all.

A modest amount of time per device. Water is off to the protected system during the test, which for commercial premises means scheduling around operations.

Multiple devices at one property are usually done in a single visit.

It has to be repaired and retested, usually within a deadline set by the water department.

Most failures are repairable with a rebuild kit, new seals, discs and springs, which is much cheaper than replacement.

Almost certainly freeze damage. An outdoor assembly left charged through a Massachusetts winter will very likely be destroyed.

Winterising, blowing the system out and draining and protecting the assembly, costs far less than the repair.

Closed heating systems contain non-potable water with inhibitor and corrosion products, and the fill line is a direct cross-connection, so protection is required.

Systems with chemical treatment or glycol typically need an RPZ.

The relief valve is doing its job, which means one of the check valves is fouled or failed, or system pressure conditions are causing it.

It needs testing and probably a rebuild. Do not plug or cap the relief discharge under any circumstances.

Worth establishing your position before the water department does. Enforcement mechanisms include notices and, in some municipalities, service interruption.

A test, any necessary repair, a retest and a filed report brings you current.

Tested, repaired, retested and filed on time